46 C.F.R. · Shipping
46 C.F.R. § 95.16.25

Manifold and cylinder arrangements.

Title 46 C.F.R. ● ACTIVE Primary Source
Regulatory Text

46 C.F.R. § 95.16.25 — Manifold and cylinder arrangements.

§ 95.16–25 Manifold and cylinder arrangements. (a) A check valve must be provided between each cylinder and manifold or distribution piping. The valve must be permanently marked to indicate the direction of flow. (b) If the same cylinder is used to protect more than one space, normally, closed stop valves must be provided to direct the agent into each protected space. (c) Each cylinder must be fabricated, tested, and marked in accordance with 46 CFR 147.60(b) and 49 CFR part 180. (d) The cylinders in a common manifold must be: (1) Of the same size; (2) Filled with the same amount of agent; and (3) Pressurized to the same working pressure.

Source: ecfr.gov · govinfo.gov — public domain Official Source ↗
Root-LD Entity Data
◈ Machine-Readable Provenance Record Root-LD v1.0 · boisestandard.org
Federation ID
BS-CFR46-SEC-F81862
Entity Class
REGULATION / FEDERAL-CFR-SECTION
Domain Signature
boisestandard.org
Citation
46 C.F.R. § 95.16.25
Corpus
CFR — Code of Federal Regulations
Status
✓ ACTIVE
Source
PRIMARY-SOURCE
Source Verified
✓ TRUE
Content Hash
5643137e64abad06...
Semantic Edges
Pending — corpus passes queued
The regulatory text of 46 C.F.R. § 95.16.25 is reproduced from the official Code of Federal Regulations as published by the Office of the Federal Register and the National Archives and Records Administration.
Navigate Corpus — Title 46 C.F.R.
◈ Provenance
boisestandard.org United States Law CFR Title 46 46 C.F.R. § 95.16.25