33 C.F.R. · Navigation and Navigable Waters
33 C.F.R. § 127.607

Fire main systems.

Title 33 C.F.R. ● ACTIVE Primary Source
Regulatory Text

33 C.F.R. § 127.607 — Fire main systems.

§ 127.607 Fire main systems. (a) Each marine transfer area for LNG must have a fire main system that provides at least two water streams to each part of the LNG transfer piping and connections, one of which must be from a single length of hose or from a fire monitor. (b) The fire main must have at least one isolation valve at each branch connection and at least one isolation valve downstream of each branch connection to isolate damaged sections. (c) The fire main system must have the capacity to supply— (1) Simultaneously all fire hydrants, standpipes, and fire monitors in the system; and (2) At a Pitot tube pressure of 618 kilonewtons per square meter (75 p.s.i.), the two outlets having the greatest pressure drop between the source of water and the hose or monitor nozzle, when only those two outlets are open. (d) If the source of water for the fire main system is capable of supplying a pressure greater than the system's design working pressure, the system must have at least one pressure relief device. (e) Each fire hydrant or standpipe must have at least one length of hose of sufficient length to meet paragraph (a) of this section. (f) Each length of hose must— (1) Be 1 1/2 inches or more in diameter and 30.5 meters (100 feet) or less in length; (2) Be on a hose rack or reel; (3) Be connected to the hydrant or standpipe at all times; and (4) Have a Coast Guard approved combination solid stream and water spray fire hose nozzle. [CGD 78-038, 53 FR 3376, Feb. 7, 1988, as amended at CGD 88-049, 60 FR 39796, Aug. 3, 1995]

Source: ecfr.gov · govinfo.gov — public domain Official Source ↗
Root-LD Entity Data
◈ Machine-Readable Provenance Record Root-LD v1.0 · boisestandard.org
Federation ID
BS-CFR33-SEC-996D99
Entity Class
REGULATION / FEDERAL-CFR-SECTION
Domain Signature
boisestandard.org
Citation
33 C.F.R. § 127.607
Corpus
CFR — Code of Federal Regulations
Status
✓ ACTIVE
Source
PRIMARY-SOURCE
Source Verified
✓ TRUE
Content Hash
734d27204c60b197...
Semantic Edges
Pending — corpus passes queued
The regulatory text of 33 C.F.R. § 127.607 is reproduced from the official Code of Federal Regulations as published by the Office of the Federal Register and the National Archives and Records Administration.
Navigate Corpus — Title 33 C.F.R.
◈ Provenance
boisestandard.org United States Law CFR Title 33 33 C.F.R. § 127.607