30 C.F.R. · Mineral Resources
30 C.F.R. § 77.800.1

Testing, examination, and maintenance of circuit breakers; procedures.

Title 30 C.F.R. ● ACTIVE Primary Source
Regulatory Text

30 C.F.R. § 77.800.1 — Testing, examination, and maintenance of circuit breakers; procedures.

§ 77.800–1 Testing, examination, and maintenance of circuit breakers; procedures. (a) Circuit breakers and their auxiliary devices protecting high-voltage circuits to portable or mobile equipment shall be tested and examined at least once each month by a person qualified as provided in § 77.103. (b) Tests shall include: (1) Breaking continuity of the ground check conductor where ground check monitoring is used; and, (2) Actuating any of the auxiliary protective relays. (c) Examination shall include visual observation of all components of the circuit breaker and its auxiliary devices, and such repairs or adjustments as are indicated by such tests and examinations shall be carried out immediately.

Source: ecfr.gov · govinfo.gov — public domain Official Source ↗
Root-LD Entity Data
◈ Machine-Readable Provenance Record Root-LD v1.0 · boisestandard.org
Federation ID
BS-CFR30-SEC-23650F
Entity Class
REGULATION / FEDERAL-CFR-SECTION
Domain Signature
boisestandard.org
Citation
30 C.F.R. § 77.800.1
Corpus
CFR — Code of Federal Regulations
Status
✓ ACTIVE
Source
PRIMARY-SOURCE
Source Verified
✓ TRUE
Content Hash
10d50316b7773b4a...
Semantic Edges
Pending — corpus passes queued
The regulatory text of 30 C.F.R. § 77.800.1 is reproduced from the official Code of Federal Regulations as published by the Office of the Federal Register and the National Archives and Records Administration.
Navigate Corpus — Title 30 C.F.R.
◈ Provenance
boisestandard.org United States Law CFR Title 30 30 C.F.R. § 77.800.1