Regulatory Text
30 C.F.R. § 75.801 — Grounding resistors.
§ 75.801 Grounding resistors. [Statutory Provisions] The grounding resistor, where required, shall be of the proper ohmic value to limit the voltage drop in the grounding circuit external to the resistor to not more than 100 volts under fault conditions. The grounding resistor shall be rated for maximum fault current continuously and insulated from ground for a voltage equal to the phase-to-phase voltage of the system.
Source: ecfr.gov · govinfo.gov — public domain
Official Source ↗
Root-LD Entity Data
◈ Machine-Readable Provenance Record
Root-LD v1.0 · boisestandard.org
Federation ID
BS-CFR30-SEC-F6082E
Entity Class
REGULATION / FEDERAL-CFR-SECTION
Domain Signature
boisestandard.org
Citation
30 C.F.R. § 75.801
Corpus
CFR — Code of Federal Regulations
Status
✓ ACTIVE
Source
PRIMARY-SOURCE
Source Verified
✓ TRUE
Content Hash
f3d76542192b47a4...
Semantic Edges
Pending — corpus passes queued
The regulatory text of 30 C.F.R. § 75.801 is reproduced from the official Code of Federal Regulations as published by the Office of the Federal Register and the National Archives and Records Administration.
Navigate Corpus — Title 30 C.F.R.
Title 30 — Mineral Resources
30 C.F.R. § 1.130 C.F.R. § 1.230 C.F.R. § 1.330 C.F.R. § 3.130 C.F.R. § 5.1030 C.F.R. § 5.3030 C.F.R. § 5.4030 C.F.R. § 5.5030 C.F.R. § 6.130 C.F.R. § 6.230 C.F.R. § 6.1030 C.F.R. § 6.2030 C.F.R. § 6.3030 C.F.R. § 7.130 C.F.R. § 7.230 C.F.R. § 7.330 C.F.R. § 7.430 C.F.R. § 7.530 C.F.R. § 7.630 C.F.R. § 7.730 C.F.R. § 7.830 C.F.R. § 7.930 C.F.R. § 7.1030 C.F.R. § 7.2130 C.F.R. § 7.2230 C.F.R. § 7.2330 C.F.R. § 7.2430 C.F.R. § 7.2530 C.F.R. § 7.2630 C.F.R. § 7.27
30 C.F.R. — public domain
← All Legislation