30 C.F.R. · Mineral Resources
30 C.F.R. § 57.22207

Booster fans (I-A, II-A, III, and V-A mines).

Title 30 C.F.R. ● ACTIVE Primary Source
Regulatory Text

30 C.F.R. § 57.22207 — Booster fans (I-A, II-A, III, and V-A mines).

§ 57.22207 Booster fans (I-A, II-A, III, and V-A mines). (a) Booster fans shall be approved by MSHA under the applicable requirements of 30 CFR part 18, and be— (1) Provided with an automatic signal device located so that it can be seen or heard by a person designated by the mine operator to give an alarm when the fan stops or when methane reaches the following levels: (i) 1.0 percent at the fan in Subcategory I-A, Category III, and Subcategory V-A mines; and (ii) 0.5 percent at the fan in Subcategory II-A mines. (2) Equipped with a device that automatically deenergizes power in affected workings should the fan stop; and (3) Equipped with starting and stopping controls located at the fan and at another accessible remote location. (b) Booster fan installations, except for booster fans installed in ducts, shall be— (1) Provided with doors which open automatically when all fans in the installation stop; and (2) Provided with an air lock when passage through the fan bulkhead is necessary.

Source: ecfr.gov · govinfo.gov — public domain Official Source ↗
Root-LD Entity Data
◈ Machine-Readable Provenance Record Root-LD v1.0 · boisestandard.org
Federation ID
BS-CFR30-SEC-3DA2BB
Entity Class
REGULATION / FEDERAL-CFR-SECTION
Domain Signature
boisestandard.org
Citation
30 C.F.R. § 57.22207
Corpus
CFR — Code of Federal Regulations
Status
✓ ACTIVE
Source
PRIMARY-SOURCE
Source Verified
✓ TRUE
Content Hash
3e4e4876da30b7d1...
Semantic Edges
Pending — corpus passes queued
The regulatory text of 30 C.F.R. § 57.22207 is reproduced from the official Code of Federal Regulations as published by the Office of the Federal Register and the National Archives and Records Administration.