7-4-5: AMENDMENTS:

Municipal Law ● Active Eagle, Idaho Ada County
Ordinance Text

7-4-5: AMENDMENTS:

7-4-5: AMENDMENTS:
IECC section 201.3 is amended to read as follows:
201.3 Terms Defined In Other Codes. Where terms are not defined in this code and are defined in the currently adopted editions in the international building code, national electrical code, international fire code, international fuel gas code, international mechanical code or the 2009 Idaho state plumbing code, such terms shall have meanings ascribed to them as in those codes.
Table 402.1.1 Insulation And Fenestration Requirements By Component is amended as follows:
   a.   Delete the values contained in table R402.1.1 (table N1102.1.1) for climate zone "5 and marine 4" and climate zone "6" and replace with the following:
   TABLE R402.1.1
   INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENT
 
Climate Zone
Fenestrati on U-Factor
Skylight U-Factor
Glazed Fenestrati on SHGC
Ceiling R-Value
Wood Framed Wall R-Value
Mass Wall R-Value
Floor R-Value
Basement Wall R-Value
Slab R-Value
Crawlspa ce Wall R-Value
5 and marine 4
0.35
0.60
NR
38
20 or 13+5h
13/17
30g
10/13
10, 2 ft
10/13
6
0.35
0.60
NR
49
20 or 13+5h
15/19
30g
15/19
10, 4 ft
10/13
         b.   Add the following footnote to the title of table 402.1.1 Insulation And Fenestration Requirements By Component:
   k.   For residential log home building thermal envelope construction requirements see section 402.6.
Table R402.1.3 delete the values contained in table 402.1.3 (table N1102.1.3) for climate zone "5 and marine 4" and climate zone "6" and replace with the following:
   TABLE R402.1.3
   EQUIVALENT U-FACTORS
 
Climate Zone
Fenestration U-Factor
Skylight U-Factor
Ceiling R-Value
Wood Framed Wall R-Value
Mass Wall R-Value
Floor R-Value
Basement Wall R-Value
Crawl-space Wall R-Value
5 and marine 4
0.35
0.60
0.030
0.057
0.082
0.033
0.059
0.065
6
0.35
0.60
0.026
0.057
0.060
0.033
0.050
0.065
Table R402.2.6 delete table R402.2.6 and replace with the following:
      TABLE R402.2.6
      STEEL-FRAME CEILING, WALL AND FLOOR INSULATION
      (R-VALUE)
Wood Frame R-Value Requirement
Cold-Formed Steel Equivalent R-Valuea
Wood Frame R-Value Requirement
Cold-Formed Steel Equivalent R-Valuea
Steel Truss Ceilings
R-30
R-38 or R-30 + 3 or R-26 = 5
R-38
R-49 or R-38 + 3
R-49
R-38 + 5
Steel Joist Ceilings
R-30
R-38 in 2 x 4 or 2 x 6 or 2 x 8 R-49 in any framing
R-38
R-49 in 2 x 4 or 2 x 6 or 2 x 8 or 2 x 10
Steel Framed Wall
R-13
R-13 + 5 or R-15 + 4 or R-21 + 3 or R-0 + 10
R-19
R-13 + 9 or R-19 + 8 or R-25 + 7
R-21
R-13 + 10 or R-19 + 9 or R-25 + 8
Steel Joist Floor
R-13
R-19 in 2 x 6
R-19 + 6 in 2 x 8 or 2 x 10
R-19
R-19 + 6 in 2 x 6
R-19 + 12 in 2 x 8 or 2 x 10
   a.   Cavity insulation R-value is listed first, followed by continuous insulation R-value.
   b.   Insulation exceeding the height of the framing shall cover the framing.
Section 402.4.3 Fireplaces shall be deleted and replaced with the following:
402.4.3 Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers and outdoor combustion air.
Section 402.6 Residential Log Home Thermal Envelope shall be an added section as follows:
402.6 Residential Log Home Thermal Envelope. Residential log home construction shall comply with sections 401 (General), 402.4 (Air Leakage), 402.5 (Maximum Fenestration U-Factor and SHGC), 403.1 (Controls), 403.2.2 (Sealing), 403.2.3 (Building Cavities), sections 403.3 through 403.9 (referred to as the mandatory provisions), section 404 (Electrical Power and Lighting Systems), and either subparagraph 004.04.b.i, ii, or iii, as follows:
i. Sections 402.2 through 402.3, 403.2.1, 404.1 and table 402.6;
ii. Section 405 Simulated Performance Alternative (Performance); or
iii. REScheck (U.S. department of energy building codes program).
Table 402.6 Log Home Prescriptive Thermal Envelope By Component is an added table as follows:
 
Climate Zone
Fenestrati on U-Factora
Skylight U-Factor
Glazed Fenestrati on SHGC
Ceiling R-Value
Min Average Log Size In Inches
Floor Value
Basement Wall R-Valued
Slab R-Value & Depthb
Crawlspace Wall R-Valued
5,6 - High efficiency equipment pathc
0.32
0.60
NR
49
5
30
15/19
10, 4 ft.
10/13
5
0.32
0.60
NR
49
8
30
10/13
10, 2 ft.
10/13
6
0.30
0.60
NR
49
8
30
15/19
10, 4 ft.
10/13
a.   The fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration.
b.   R-5 shall be added to the required slab edge R-values for heated slabs.
c.   90% AFUE natural gas or propane. 84% AFUE oil, or 15 SEER heat pump heating equipment (zonal electric resistance heating equipment such as electric resistance heating equipment as the sole source for heating is considered compliant with the high efficiency equipment path).
d.   "15/19" means R-15 continuous insulated sheathing on the interior or exterior of the home or R-19 cavity insulation at the interior of the basement wall. "15/19" shall be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulated sheathing on the interior or exterior of the home. "10/13" means R-10 continuous insulated sheathing on the interior or exterior of the home or R-13 cavity insulation at the interior of the basement wall.
(Ord. 728, 1-27-2015)
Source: American Legal Publishing — codelibrary.amlegal.com — public domain Official Source ↗
Root-LD Entity Data
◈ Machine-Readable Provenance Record boisestandard.org · municipal corpus
Federation ID
bs-aml-eag-ef3cfb3d73092b89
Doc ID
0-0-0-9317
Domain Signature
boisestandard.org
Jurisdiction
Eagle, Idaho — United States
City
Eagle
County
Ada County
Publisher
American Legal Publishing
Source Verified
✓ TRUE
Navigate — Eagle City Code of Eagle
◈ Provenance
boisestandard.org United States Idaho Eagle Eagle Municipal Code 7-4-5: AMENDMENTS: