5-12-46: IFC AMENDMENT, SECTION 914.3.1.2, WATER SUPPLY TO REQUIRED FIRE PUMPS:

Municipal Law ● Active Boise, Idaho Ada County
Ordinance Text

5-12-46: IFC AMENDMENT, SECTION 914.3.1.2, WATER SUPPLY TO REQUIRED FIRE PUMPS:

5-12-46: IFC AMENDMENT, SECTION 914.3.1.2, WATER SUPPLY TO REQUIRED FIRE PUMPS:
   914.3.1.2 Water supply to required fire pumps. In all buildings that are more than 420 feet (128 m) in building height, and buildings of Type IV-A and IV-B construction that are more than 120 feet (36.6 m) in building height, required fire pumps shall be supplied by connections to not fewer than two water mains located in different streets. Separate supply piping shall be provided between each connection to the water main and the pumps. Each connection and the supply piping between the connection and the pumps shall be sized to supply the flow and pressure required for the pumps to operate.
      Exception: Two connections to the same main shall be permitted provided that the main is valved such that an interruption can be isolated so that the water supply will continue without interruption through not fewer than one of the connections.
(Ord. 50-21, 11-30-2021, eff. 1-1-2022)
Source: American Legal Publishing — codelibrary.amlegal.com — public domain Official Source ↗
Root-LD Entity Data
◈ Machine-Readable Provenance Record boisestandard.org · municipal corpus
Federation ID
bs-aml-boi-f93644e397278d0b
Doc ID
0-0-0-78671
Domain Signature
boisestandard.org
Jurisdiction
Boise, Idaho — United States
City
Boise
County
Ada County
Publisher
American Legal Publishing
Source Verified
✓ TRUE
Navigate — Boise City Code of Boise City
◈ Provenance
boisestandard.org United States Idaho Boise Boise Municipal Code 5-12-46: IFC AMENDMENT, SECTION 914.3.1.