5-12-42: IFC AMENDMENT, ADD SECTION 906.5.1, MULTI- STORY INSTALLATION NEAR STAIRWELLS:
906.5.1 Multi-Story Installation Near Stairwells. In multi-story buildings, at least one 2A fire extinguisher shall be located adjacent to the stairway at each floor level. Extinguishers shall not be placed on half landings unless approved by the fire code official.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)
Source: American Legal Publishing — codelibrary.amlegal.com — public domain
Official Source ↗
Root-LD Entity Data
◈ Machine-Readable Provenance Record
boisestandard.org · municipal corpus
Federation ID
bs-aml-boi-28211809e071bf39
Doc ID
0-0-0-78658
Domain Signature
boisestandard.org
Jurisdiction
Boise, Idaho — United States
City
Boise
County
Ada County
Publisher
American Legal Publishing
Source Verified
✓ TRUE
Navigate — Boise City Code of Boise City
← 5-12-41: IFC AMENDMENT, ADD SECTION 904.7.2, USE OF FOA
5-12-43: IFC AMENDMENT, ADD SECTION 907.6.6.3, SINGLE C →
Nearby Sections
5-12-37: IFC AMENDMENT, ADD SECTION 903.3.1.35-12-38: IFC AMENDMENT, ADD SECTION 903.3.5.35-12-39: IFC AMENDMENT, ADD SECTION 903.3.5.45-12-40: IFC AMENDMENT, SECTION 903.4.3, FLOO5-12-41: IFC AMENDMENT, ADD SECTION 904.7.2, 5-12-42: IFC AMENDMENT, ADD SECTION 906.5.1, 5-12-43: IFC AMENDMENT, ADD SECTION 907.6.6.35-12-44: IFC AMENDMENT, ADD SECTION 907.6.7, 5-12-45: IFC AMENDMENT, ADD SECTION 912.2.3, 5-12-46: IFC AMENDMENT, SECTION 914.3.1.2, WA5-12-47: IFC AMENDMENT, ADD SECTION 914.8.3.35-12-48: IFC AMENDMENT, SECTION 1101.1, SCOPE5-12-49: IFC AMENDMENT, SECTION 2007.6, FOAM 5-12-50: IFC AMENDMENT, SECTION 3304.5, FIRE 5-12-51: IFC AMENDMENT, ADD SECTION 3304.9, F
Boise Municipal Code — public domain
← Boise Code Index