Ordinance Text
5-12-38: IFC AMENDMENT, ADD SECTION 903.3.5.3, CONTROL VALVE LOCATION:
903.3.5.3 Control Valve Location. Fire sprinkler system main control valves shall be located in a fire sprinkler riser room that is separated from the building on all sides by a one-hour fire barrier, horizontal assembly, or both, including opening and penetration protection, as defined by the Building Code. The fire sprinkler riser room shall be provided with an exterior door that opens directly into the room.
Exception: Sprinkler systems provided with post indicator valves located in an approved location.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021; amd. Ord. 10-23, 3-7-2023)
Source: American Legal Publishing — codelibrary.amlegal.com — public domain
Official Source ↗
Root-LD Entity Data
◈ Machine-Readable Provenance Record
boisestandard.org · municipal corpus
Federation ID
bs-aml-boi-86a9378b7cd67709
Doc ID
0-0-0-78643
Domain Signature
boisestandard.org
Jurisdiction
Boise, Idaho — United States
City
Boise
County
Ada County
Publisher
American Legal Publishing
Source Verified
✓ TRUE
Navigate — Boise City Code of Boise City
← 5-12-37: IFC AMENDMENT, ADD SECTION 903.3.1.3.1, NFPA 1
5-12-39: IFC AMENDMENT, ADD SECTION 903.3.5.4, DEPTH OF →
Nearby Sections
5-12-33: IFC AMENDMENT, ADD SECTION 507.5.7, 5-12-34: IFC AMENDMENT, SECTION 701.6, OWNER’5-12-35: IFC AMENDMENT, ADD SECTION 901.4.2.15-12-36: IFC AMENDMENT, ADD SECTION 903.3.1.15-12-37: IFC AMENDMENT, ADD SECTION 903.3.1.35-12-38: IFC AMENDMENT, ADD SECTION 903.3.5.35-12-39: IFC AMENDMENT, ADD SECTION 903.3.5.45-12-40: IFC AMENDMENT, SECTION 903.4.3, FLOO5-12-41: IFC AMENDMENT, ADD SECTION 904.7.2, 5-12-42: IFC AMENDMENT, ADD SECTION 906.5.1, 5-12-43: IFC AMENDMENT, ADD SECTION 907.6.6.35-12-44: IFC AMENDMENT, ADD SECTION 907.6.7, 5-12-45: IFC AMENDMENT, ADD SECTION 912.2.3, 5-12-46: IFC AMENDMENT, SECTION 914.3.1.2, WA5-12-47: IFC AMENDMENT, ADD SECTION 914.8.3.3
Boise Municipal Code — public domain
← Boise Code Index