Boise, Idaho · Municipal Code
City Code of Boise City · Ada County

5-12-33: IFC AMENDMENT, ADD SECTION 507.5.7, FIRE HYDRANT SUPPLY CONNECTIONS:

Municipal Law ● Active Boise, Idaho Ada County
Ordinance Text

5-12-33: IFC AMENDMENT, ADD SECTION 507.5.7, FIRE HYDRANT SUPPLY CONNECTIONS:

5-12-33: IFC AMENDMENT, ADD SECTION 507.5.7, FIRE HYDRANT SUPPLY CONNECTIONS:
   507.5.7 Fire Hydrant Supply Connections. Fire hydrants and fire suppression systems shall be supplied with independent connections to the municipal supply mains. Looped private fire service mains that are supplied from two (2) points of connection to municipal supply mains shall be allowed.
   Exception: Where sprinkler hydraulic calculations show that a minimum of 500 GPM can be provided at the hydrant while simultaneously supplying the fire sprinkler system hydraulic demand plus required hose allowance. Approval of this exception must be approved by the water purveyor prior to submitting for permit. The approval letter must be included in the fire sprinkler permit submittal package.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021; amd. Ord. 7-25, 2-25-2025)
Source: American Legal Publishing — codelibrary.amlegal.com — public domain Official Source ↗
Root-LD Entity Data
◈ Machine-Readable Provenance Record boisestandard.org · municipal corpus
Federation ID
bs-aml-boi-367e7ffc30db811d
Doc ID
0-0-0-78626
Domain Signature
boisestandard.org
Jurisdiction
Boise, Idaho — United States
City
Boise
County
Ada County
Publisher
American Legal Publishing
Source Verified
✓ TRUE
Navigate — Boise City Code of Boise City
◈ Provenance
boisestandard.org United States Idaho Boise Boise Municipal Code 5-12-33: IFC AMENDMENT, ADD SECTION 507.