9-1A-55: IBC BUILDING CODE AMENDMENT, SECTION 1608.1, SNOW LOADS:

Municipal Law ● Active Boise, Idaho Ada County
Ordinance Text

9-1A-55: IBC BUILDING CODE AMENDMENT, SECTION 1608.1, SNOW LOADS:

9-1A-55: IBC BUILDING CODE AMENDMENT, SECTION 1608.1, SNOW LOADS:
   1608.1 General. Design snow loads shall be determined in accordance with Chapter 7 of ASCE 7, but the design roof load, regardless of roof slope, shall not be less than a uniform snow load of pm = 25 psf. This minimum roof snow load is a separate load case. It need not be used in determining or in combination with drift, sliding, unbalanced, rain-on-snow surcharge, or partial loads. These loads shall be considered as required by ASCE 7 and IBC section 1608.2 as amended. See Figure A showing two examples of required load cases.
   FIGURE A
(Ord. 44-17, 12-19-2017, eff. 1-1-2018; amd. Ord. 39-20, 12-1-2020, eff. 1-1-2021)